sales@yuanning.com
0717-6683666
Online Store
<strong>Compliant station construction, use Mituo</strong> <strong>Compliant station construction, use Mituo</strong>

Compliant station construction, use Mituo

For 12 years, we focus on the r & D of mituo enterprise station building system, providing you with compliance, safety and professional official website solutions!

<strong>Website compliance, choose Mituo</strong> <strong>Website compliance, choose Mituo</strong>

Website compliance, choose Mituo

According to the

Home / / YUANNING SRP300PX PT Resonance Elimination Device

YUANNING SRP300PX PT Resonance Elimination Device

2026-05-07 13:03:42 views
This is a 2-in-1 device combining microcomputer PT resonance elimination and microcomputer PT protection & control. It features PT resonance elimination, overvoltage protection, undervoltage protection, voltage monitoring, insulation monitoring, and broken wire alarm functions.

Inquire about this product

Application Scope and Features

012-in-1 Design

This is a 2-in-1 device combining microcomputer PT resonance elimination and microcomputer PT protection & control. It features PT resonance elimination, overvoltage protection, undervoltage protection, voltage monitoring, insulation monitoring, and broken wire alarm functions.

02PT Protection Solution

This device is a newly developed intelligent resonance elimination device specifically designed to prevent voltage transformer (PT) burnout or even explosion accidents caused by ferromagnetic resonance, which frequently occur in power departments and user facilities.

03Advanced Technology

The device uses a 32-bit high-speed, large-capacity microcontroller and high-speed, high-precision AD converter. Combined with intelligent software and high-power, non-contact resonance elimination components, it achieves PT resonance elimination, voltage monitoring, and PT protection functions.

04Harmonic Monitoring

The device performs real-time, high-precision collection of PT open-delta voltage components at four frequencies: 17HZ, 25HZ, 50HZ, and 150HZ. It can distinguish overvoltage, ferromagnetic resonance, and single-phase grounding, with communication interface for transmitting fault information to relevant departments, suitable for unattended substations.

05Analog Inputs

4 analog input channels for collecting three-phase bus voltage and zero-sequence voltage data.

06Digital Inputs

3 programmable digital input channels to meet various PT cabinet switch input requirements. Input names and functions can be programmed according to actual on-site wiring, ensuring both convenience and flexibility.

07Relay Outputs

6 relay output contacts, including 1 channel for PT resonance elimination output.

08Communication Interface

High-speed RS485 communication interface with optoelectronic isolation and lightning protection. Standard communication protocol with communication rate up to 38400bps.

09User-friendly Interface

Large-screen LCD display with Chinese menu operation for friendly human-machine interface. Settings, sampling data, control word meanings, digital inputs, and fault information are all displayed in Chinese for convenient on-site setting adjustment and fault query.

10Fault Recording

Fault recording and waveform capture functions display fault occurrence time, fault current and voltage data, and fault waveforms directly on the LCD screen.

11Precision Clock

High-precision clock chip enables accurate recording of various fault information. Also supports receiving network time synchronization from distribution master station.

Main Protection Functions

PT Voltage & Harmonic Monitoring
PT Resonance Elimination
Line Ground Fault (Trip/Alarm selectable)
Zero-sequence Overvoltage Protection (Trip/Alarm)
Line Overvoltage Protection (Trip/Alarm)
Line Undervoltage Protection (Trip/Alarm)
PT Disconnection Detection & Alarm
3 Programmable Input Protection